SECTION 07 30 70
STEEP SLOPE ROOFING UNDERLAYMENTS
Display hidden notes to specifier. (Don't know how? Click Here)
Copyright 2019 - 2019 ARCAT, Inc. - All rights reserved
- 1 GENERAL
- SECTION INCLUDES
-
-
- Roofing Underlayments of the following types:
- Premium high temperature roofing underlayment. (RoofTopGuard II)
- High temperature roofing underlayment. (RoofTopGuard SA HT)
- Standard synthetic roofing underlayment. (Roofers Choice II Synfelt, Petex 15)
- Breathable roofing and wall underlayment. (AirOutshield SA 280, AirOutshield Roof)
- Wall Underlayment. (AirOutshield Wall, AirOutshield UV, AirOutshield SA 280)
- Roofing Underlayments of the following types:
- RELATED SECTIONS
-
-
-
- Section 06 10 00 - Rough Carpentry.
- Section 07 31 13 - Asphalt Shingles.
- Section 07 41 13 - Metal Roof Panels.
- Section 07 46 16 - Aluminum Siding.
- Section 07 62 00 - Sheet Metal Flashing and Trim.
- REFERENCES
-
-
-
- ASTM International (ASTM):
- ASTM D226 - Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing.
- ASTM D570 - Standard Test Method for Water Absorption of Plastics.
- ASTM D751 - Standard Test Methods for Coated Fabrics.
- ASTM D882 - Standard Test Method for Tensile Properties of Thin Plastic Sheeting.
- ASTM D903 - Standard Test Method for Peel or Stripping Strength of Adhesive Bonds.
- ASTM D1938 - Standard Test Method for Tear-Propagation Resistance, Trouser Tear, of Plastic Film and Thin Sheeting by a Single-Tear Method.
- ASTM D1970 - Standard Specification for Self-Adhering Polymer Modified Bituminous Sheet Materials Used as Steep Roofing Underlayment for Ice Dam Protection.
- ASTM D2523 - Standard Practice for Testing Load-Strain Properties of Roofing Membranes.
- ASTM D4073 - Standard Test Method for Tensile-Tear Strength of Bituminous Roofing Membranes.
- ASTM D4518 - Standard Test Methods for Measuring Static Friction of Coating Surfaces.
- ASTM D4533 - Standard Test Method for Trapezoid Tearing Strength of Geotextiles.
- ASTM D4586 - Standard Specification for Asphalt Roof Cement, Asbestos-Free.
- ASTM D4869 - Standard Specification for Asphalt-Saturated Organic Felt Underlayment Used in Steep Slope Roofing.
- ASTM D5034 - Standard Test Method for Breaking Strength and Elongation of Textile Fabrics, Grab Test.
- ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials.
- ASTM E96 - Standard Test Methods for Water Vapor Transmission of Materials.
- ASTM E108 - Standard Test Methods for Fire Tests of Roof Coverings.
- ASTM E331 - Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference.
- ASTM E2178 - Standard Test Method for Air Permeance of Building Materials.
- ASTM E2357 - Standard Test Method for Determining Air Leakage Rate of Air Barrier Assemblies.
- Dade County Protocols:
- Dade County PA 104 - Test Procedure for Nail-On Underlayments for Use in Discontinuous Roof Systems.
- Notice of Acceptance, Miami Dade: NOA 18-0829.08.
- Deutsches Institut fUr Normung or German Institute for Standardization (DIN):
- DIN EN 13859 - Flexible Sheets for Waterproofing - Definitions and Characteristics of Underlays.
- Florida Building Code (FBC):
- FBC: Approval Number FL 27703
- International Code Council (ICC):
- ICC AC 38 - Acceptance Criteria for Water-Resistive Barriers.
- ICC/EM AC 48 - Acceptance Criteria for Self-Adhered Roof Underlayments for Use as Ice Barriers.
- ICC AC 188 - Acceptance Criteria for Roof Underlayments.
- ICC AC 207 - Acceptance Criteria for Polypropylene Roof Underlayments.
- ICC-ES: ESR-4384 - Evaluation Report for Underlayment Specialties Plus LLC. RoofTopGuard SA HT.
- ASTM International (ASTM):
- SUBMITTALS
- Submit under provisions of Section 01 30 00 - Administrative Requirements.
- Product Data:
- Manufacturer's data sheets on each product to be used.
- Preparation instructions and recommendations.
- Storage and handling requirements and recommendations.
- Typical installation methods.
- Shop Drawings: Include details of materials, construction and finish. Include relationship with adjacent construction.
- QUALITY ASSURANCE
- Manufacturer Qualifications: Company specializing in manufacturing products specified in this section with a minimum five years documented experience.
- Installer Qualifications: Company specializing in performing Work of this section with minimum two years documented experience with projects of similar scope and complexity.
- Source Limitations: Provide each type of product from a single manufacturing source to ensure uniformity.
-
-
-
- Mock-Up: Construct a mock-up with actual materials in sufficient time for Architect's review and to not delay construction progress. Locate mock-up as acceptable to Architect and provide temporary foundations and support.
- Intent of mock-up is to demonstrate quality of workmanship and visual appearance.
- If mock-up is not acceptable, rebuild mock-up until satisfactory results are achieved.
- Retain mock-up during construction as a standard for comparison with completed work.
- Do not alter or remove mock-up until work is completed or removal is authorized.
- Mock-Up: Construct a mock-up with actual materials in sufficient time for Architect's review and to not delay construction progress. Locate mock-up as acceptable to Architect and provide temporary foundations and support.
- PRE-INSTALLATION CONFERENCE
- Convene a conference approximately two weeks before scheduled commencement of the Work. Attendees shall include Architect, Contractor and trades involved. Agenda shall include schedule, responsibilities, critical path items and approvals.
- DELIVERY, STORAGE, AND HANDLING
- Store and handle in strict compliance with manufacturer's written instructions and recommendations.
- Protect from damage due to weather, excessive temperature, and construction operations.
- PROJECT CONDITIONS
- Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.
- WARRANTY
- Manufacturer's Warranty: Provide manufacturer's standard limited warranty.
-
- 2 PRODUCTS
- MANUFACTURERS
- Acceptable Manufacturer: Underlayment Specialties Plus (USP), which is located at: 805 W. 5th St. Unit # 10A; Lansdale, PA 19446; Toll Free Tel: 844-767-4963; Email:request info (info@uspunderlayment.com); Web:https://www.uspunderlayment.com
- MANUFACTURERS
-
-
- Substitutions: Not permitted.
- Requests for substitutions will be considered in accordance with provisions of Section 01 60 00 - Product Requirements.
-
-
- PREMIUM HIGH TEMPERATURE ROOFING UNDERLAYMENT
- Performance Requirements:
- Approvals:
- ICC-ES ESR 2928. For Underlayment Specialties Plus LLC.
- FBC: Approval Number FL12145.
- ICBO: ITS 484-1932 and 484-2143
- CAN/CSA: A220.1
- Dimensional Stability, tested at 180 degrees F (82 degrees C) for six hours per Dade County PA 104: No tears, cracks, shrinking, or wrinkling.
- Tear Resistance, per ASTM D1938: Minimum average result of 118 pounds (5.978 kg).
- Breaking Strength, New, per ASTM D2523: Minimum average result of 86.82 pounds (39.38 kg).
- Elongation, New, per ASTM D2523: Minimum average result of 27 percent.
- Water Absorption, per ASTM D570: Maximum average result of 2.4 percent.
- Cold Flexibility, per ASTM 1970: No cracking.
- Ultraviolet Resistance, per ICC/EM AC 48: No peeling, chipping, cracking, flaking, pitting, or other damage.
- Accelerated Aging, per Dade County PA 104: No visible damage, passes breaking strength and elongation tests.
- Cyclic Elongation, per ICC/EM AC 48: No cracking.
- Water Vapor Transmission, per ASTM E96: Maximum average result of 0.0012 oz/sq.ft. (0.38 g/sq.m.)
- Puncture Resistance, per Dade County PA 104: No puncture.
- Slippage Resistance, per Dade County PA 104: No tears, slippage, or pulling away from fasteners.
- Static Friction, per ASTM D4518: Performs similarly to 30 lb felt.
- Water Penetration, per ASTM E331: No leakage found around fasteners when secured per instructions.
- Fire Rating, per ASTM E108 and ICC AC 207: Class A.
- Approvals:
- Basis of Design: RoofTopGuard II; as supplied by Underlayment Specialties Plus LLC.
- Description: High-strength performance roofing underlayment used on steep-sloped roofs.
- Composition: Woven HDPE with a polyethylene film laminated with black LDPE on one side and, a nonwoven polypropylene layer laminated with LDPE on the other side.
- Roll Width: 60 inches (1524 mm).
- Roll Length: 200 feet (60,960 mm).
- Color: Gray.
- Accessories:
- Sealant: Asbestos free plastic roofing cement compliant with ASTM D4586, Type I.
- Fasteners: Plastic or steel cap roofing nails with minimum 1 inch (25 mm) caps.
- Performance Requirements:
- PREMIUM HIGH TEMPERATURE ROOFING UNDERLAYMENT
-
- HIGH TEMPERATURE ROOFING UNDERLAYMENT
- Performance Requirements:
- Certifications:
- Evaluation Report: ICC-ES: ESR-4384. For Underlayment Specialties Plus LLC.
- Notice of Acceptance, Miami Dade: NOA 18-0829.08.
- FBC: Approval Number FL 27703.
- Tensile Strength, per ASTM D1970 and ASTM D2523: 71 lbf/in (12 N/mm).
- Pliability, per ICC/EM AC 48: Pass.
- Water Ponding, per ICC/EM AC 48: Pass.
- Cycling and Elongation, per ICC/EM AC 48: Pass.
- UV Exposure, per ICC/EM AC 48: Pass.
- Adhesion to Plywood at 40 degrees F (4.4 degrees C), per ASTM D903: 95 lbf/ft (1.4 N/mm).
- Adhesion to Plywood at 75 degrees F (24 degrees C), per ASTM D903: 35 lbf/ft (0.51 N/mm).
- Thermal Stability, per ASTM D1970: Pass.
- Tear Resistance, per ASTM D4073: 128 lbf (569 N).
- Sealability around Nail, per ASTM D1970: Pass.
- Waterproof Integrity after low Temp Flex, per ASTM D1970: Pass.
- Waterproof Integrity of Seam, per ASTM D1970: Pass.
- Water Vapor Transmission, per ASTM E96: 0 perm.
- Slip Resistance, per ASTM D1970: Greater than felt.
- Certifications:
- Basis of Design: RoofTopGuard SA HT; as manufactured and supplied by Underlayment Specialties Plus LLC.
- Description: Synthetic based, high-temperature, self-adhered ice and water roof underlayment used in steep slope applications.
- Composition: Polyethylene and polypropylene.
- Thickness: 0.026 inches (0.66 mm).
- Roll Width: 59 inches (1499 mm).
- Minimum Installation Temperature: 15 degrees F (Minus 9.4 degrees C).
- Service Temperature: Minus 20 to 260 degrees F (Minus 29 to 127 degrees C).
- Performance Requirements:
- HIGH TEMPERATURE ROOFING UNDERLAYMENT
-
- STANDARD SYNTHETIC ROOFING UNDERLAYMENT
-
-
- Basis of Design: Roofers Choice II Synfelt; as manufactured and supplied by Underlayment Specialties Plus LLC.
- Performance Requirements:
- Meets ASTM E108, Class A fire rating.
- Description: High strength and high temperature performance roofing underlayment used on steep sloped roofs.
- Composition: Woven HDPE fabric extrusion coated with a high coefficient of friction polyolefin blended with carbon black providing a skid-resistant finish on one side, laminated to a non-woven polypropylene fabric surface with LDPE on the other side.
- Roll Width: 60 inches (1524 mm).
- Roll Length: 200 feet (60,960 mm).
- Color: Gray.
- Performance Requirements:
- Basis of Design: Roofers Choice II Synfelt; as manufactured and supplied by Underlayment Specialties Plus LLC.
-
-
-
- Basis of Design: Petex 15; as manufactured and supplied by Underlayment Specialties Plus LLC.
- Performance Requirements:
- Tensile Strength, per ASTM D751: Minimum 78 lb (35 kg).
- Elongation, per ASTM D751: Minimum 14 percent.
- Tear Strength, Trapezoidal, per ASTM D4533: Minimum 26 lb (12 kg).
- Liquid Water Resistance, per ASTM D4869: Pass.
- UV Exposure, per ICC AC 188: Pass.
- Pliability, per ASTM D226: Pass.
- Description: High strength performance roofing underlayment used on steep sloped roofs.
- Composition: Woven HDPE fabric extrusion coated with a high coefficient of friction polyolefin blended with carbon black providing a skid-resistant finish on one side, laminated to a non-woven polypropylene fabric surface with LDPE on the other side.
- Roll Width: 60 inches (1524 mm).
- Roll Length: 200 feet (60,960 mm).
- Thickness: 0.007 inches (0.18 mm).
- Service Temperature: Minus 20 to 180 degrees F (Minus 29 to 82 degrees C).
- Performance Requirements:
- Basis of Design: Petex 15; as manufactured and supplied by Underlayment Specialties Plus LLC.
-
-
- BREATHABLE ROOFING UNDERLAYMENT
-
-
- Basis of Design: AirOutshield SA 280; as supplied by Underlayment Specialties Plus LLC.
- Performance Requirements:
- Water Vapor Permeance, per ASTM E96 - A: 12.6 perms.
- Air Leakage Resistance, per ASTM E2357: Less than 0.05.
- Flame Spread Index, per ASTM E84: 5.
- Smoke Developed Index, per ASTM E84: 5.
- Description: Fully self-adhered, micro-porous film laminate.
- Composition: Triple layer, spun bonded polypropylene.
- Roll Width: 57 inches (1448 mm).
- Thickness: 0.024 inch (0.60 mm).
- Color: Black.
- Minimum Installation Temperature: 20 degrees F (Minus 6.7 degrees C).
- Service Temperature: Minus 40 to 212 degrees F (Minus 40 to 100 degrees C).
- Accessory Materials:
- Performance Requirements:
- Basis of Design: AirOutshield SA 280; as supplied by Underlayment Specialties Plus LLC.
-
-
-
-
-
- Detail Tape: As recommended by Manufacturer.
- Eave Protection: Self adhered membrane.
- Eave Protection: High Temperature resistant underlayment.
- Fasteners: As recommended by Manufacturer.
- Ventilation Mat: Non-woven nylon with maximum 20 percent contact area or battens.
-
-
-
-
-
- Basis of Design: AirOutshield Roof; as supplied by Underlayment Specialties Plus LLC.
- Performance Requirements:
- Water Vapor Transmission, per ASTM E96: 119 perms.
- Liquid Water Transmission, per ASTM D4869: Pass.
- Pliability, per ASTM D226: Pass.
- Accelerated Aging, per ICC AC 48: Pass.
- UV Exposure, per ICC AC 48: Pass.
- Description: Breathable roofing underlayment.
- Composition: Multi-layer, spun bonded polypropylene.
- Roll Width: 57 inches (1448 mm).
- Thickness: 0.024 inch (0.60 mm).
- Color: Black.
- Accessory Materials:
- Performance Requirements:
- Basis of Design: AirOutshield Roof; as supplied by Underlayment Specialties Plus LLC.
-
-
-
-
-
- Detail Tape: As recommended by Manufacturer.
- Eave Protection: Self adhered membrane.
- Eave Protection: High Temperature resistant underlayment.
- Fasteners: As recommended by Manufacturer.
- Ventilation Mat: Non-woven nylon with maximum 20 percent contact area.
-
-
-
-
- WALL UNDERLAYMENT
-
-
- Basis of Design: AirOutshield Wall; as supplied by Underlayment Specialties Plus LLC.
- Performance Requirements:
- Water Vapor Permeance, per ASTM E96 - A: 156.1 perms.
- Tensile Strength, per ASTM D882: 27.4 lbf/in (4.79 N/mm).
- Breaking Force, MD, per ASTM D5034: 77.6 lbf (345 N).
- Flame Spread Index, per ASTM E84: 20.
- Smoke Developed Index, per ASTM E84: 185.
- Low Temperature Flexibility, per ICC AC 38: Pass.
- UV Exposure, per ICC AC 38: Pass.
- Accelerated Aging, per ICC AC 38: Pass.
- Water Ponding, per ICC AC 38: Pass.
- Air Permeance, per ICC AC 38: No air leakage at 75 Pa.
- Description: Breathable underlayment for rain screen wall systems, used as a secondary drainage plane.
- Composition: Triple layer, spun bonded polypropylene.
- Thickness: 0.023 inch (0.58 mm).
- Color:
- Top: Orange.
- Bottom: White.
- Accessory Materials:
- Performance Requirements:
- Basis of Design: AirOutshield Wall; as supplied by Underlayment Specialties Plus LLC.
-
-
-
-
-
- Tapes: As recommended by Manufacturer.
- Detail Membrane Flashing: SRP AirOutshield SA 280 flashing.
- Sealant/Adhesive: As recommended by Manufacturer.
- Fasteners: As recommended by Manufacturer.
- Ventilation Mat: Non-woven nylon with maximum 20 percent contact area.
-
-
-
-
-
- Basis of Design: AirOutshield UV; as supplied by Underlayment Specialties Plus LLC.
- Performance Requirements:
- Water Vapor Permeance, per ASTM E96 - A: 26.9 perms.
- Fire Classification, per ASTM E84: Class A.
- Air Permeance, per ASTM E2178: 0.0001 cfm/sq.ft. (0.0005 L/s.sq.m.) at 75 Pa.
- UV Resistance, per DIN EN-13859: 5000 hours exposure with a reduction in tensile of less than 5 percent.
- Description: Water and UV resistant, breathable underlayment for open joint rain screen wall systems.
- Composition: Double layer, coated polyester.
- Roll Width: 59 inches (1.5 m).
- Roll Length: 164 feet (50 m).
- Thickness: 0.023 inch (0.58 mm).
- Color: Black.
- Accessory Materials:
- Performance Requirements:
- Basis of Design: AirOutshield UV; as supplied by Underlayment Specialties Plus LLC.
-
-
-
-
-
- Tapes: As recommended by Manufacturer.
- Self-Adhered Membrane: Regular temperatures.
- Self-Adhered Membrane: High temperature.
- Fasteners: As recommended by Manufacturer.
- Ventilation Mat: Non-woven nylon with maximum 20 percent contact area.
-
-
-
-
-
- Basis of Design: AirOutshield SA 280; as supplied by Underlayment Specialties Plus LL
- Performance Requirements:
- Water Vapor Permeance, per ASTM E96 - A: 12.6 perms.
- Air Leakage Resistance, per ASTM E2357: Less than 0.05.
- Flame Spread Index, per ASTM E84: 5.
- Smoke Developed Index, per ASTM E84: 5.
- Description: Fully self-adhered, micro-porous film laminate.
- Composition: Triple layer, spun bonded polypropylene.
- Roll Width: 57 inches (1448 mm).
- Thickness: 0.024 inch (0.60 mm).
- Color: Black.
- Minimum Installation Temperature: 20 degrees F (Minus 6.7 degrees C).
- Service Temperature: Minus 40 to 212 degrees F (Minus 40 to 100 degrees C).
- Accessory Materials:
- Performance Requirements:
- Basis of Design: AirOutshield SA 280; as supplied by Underlayment Specialties Plus LL
-
-
-
-
-
- Detail Tape: As recommended by Manufacturer.
- Eave Protection: Self adhered membrane.
- Eave Protection: High Temperature resistant underlayment.
- Fasteners: As recommended by Manufacturer.
- Ventilation Mat: Non-woven nylon with maximum 20 percent contact area or battens.
-
-
-
- 3 EXECUTION
- EXAMINATION
- Do not begin installation until substrates have been properly constructed and prepared.
- If substrate preparation is the responsibility of another installer, notify Architect in writing of unsatisfactory preparation before proceeding.
- Roof Underlayments: Verify that proper roof slope exists.
- PREPARATION
- Clean surfaces thoroughly prior to installation.
- Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.
- INSTALLATION
- Install in accordance with manufacturer's instructions, approved submittals, and in proper relationship with adjacent construction.
- Prepare penetrations as recommended by Manufacturer.
- Treat seams and joints as recommended by Manufacturer.
- Install flashings and detail membranes as recommended by Manufacturer.
- Install in accordance with manufacturer's instructions, approved submittals, and in proper relationship with adjacent construction.
- FIELD QUALITY CONTROL
- Field Inspection: Coordinate field inspection in accordance with appropriate sections in Division 01.
- CLEANING AND PROTECTION
- Clean products in accordance with the manufacturer's recommendations.
- Touch-up, repair or replace damaged products before Substantial Completion.
- EXAMINATION
END OF SECTION